期刊/報告no:: International Journal of Refrigeration-Revue Internationale Du Froid, Volume 33, Issue 2, Page(s) 251-258.
摘要: This article experimentally investigates the thermal performance of a heat pump system with an ice storage subcooler. The system supplies heating and cooling demands to two greenhouses with temperature ranging 308 similar to 323 K and 273 similar to 291 K respectively and utilizes an ice storage tank to subcool the condensed refrigerant, which can enhance the system coefficient of performance (COP). The ice storage tank charges for storing ice, when the cooling load is less than the nominal cooling capacity. While the cooling load is larger than the nominal cooling capacity, the ice storage tank discharges for subcooling. The results show that in the charge mode the heat pump COP of ice storage system is 12% higher than that without ice storage tank. Under the discharge mode, the ice storage system provides the refrigerator COP 15% higher than that without ice storage tank. (C) 2009 Elsevier Ltd and IIR. All rights reserved.
URI: http://hdl.handle.net/11455/69522
ISSN: 0140-7007
文章連結: http://dx.doi.org/10.1016/j.ijrefrig.2009.11.002
Appears in Collections:期刊論文

文件中的檔案:

取得全文請前往華藝線上圖書館



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.