Please use this identifier to cite or link to this item: http://hdl.handle.net/11455/1725
標題: 空調系統溫度控制研究
On the Temperature Control of Air Conditioning Systems
作者: 張釗洋
Chang, Chuan-Yang
關鍵字: 溫度控制;PID;內模控制;IMC
出版社: 機械工程學系所
引用: 參考文獻 [1]Vlt 6000 HVAC,“Improving secondary pumping in prime /secondary pumping systems”, Technical Report 175R01- 03,Danfoss Drives A/S,1998 [2]O.J.M.Smith,“A controller to overcome dead time”, ISAJ,Vol.(2),pp.28-33,1959 [3]C. Santacesaria,R. Scattolini,“ Easy tuning of Smith predictor in presence of delay uncertainty”,Automatic a,Vol.29, pp.1595-1597,1993 [4]Z.Q.Wang and S.Skogestad,“Robust control of time-dela y systems using the smith predictor”,Int.J.Control, Vol.57(6),pp.1405- 1420,1993 [5]C.E.Garcia,M.Morari,“Internal model control 1.A unifying review and some new results”,Ind.Eng.Chem. Process Des Dev.,Vol.21,pp.308-323,1982 [6]T.H.Lee,Q.G.Wang and K.K.Tan,“Robust smith predictor control for uncertain delay systems”,AICHE,Vol.4, pp.1033-1040,1996 [7]P. Brath ,H. Rasmussen and T. H gglund,“Control of t he outlet air temperature in an air handling unit”, IEEE,UKACC International Conference on Control,1-4 Sep tember,Conference Publication No.455,pp.935-940,1998 [8]J.G.Ziegler,N.B.Nichols,“Optimum setting for automati c controllers”,ASME,Vol.64,pp.759-768,1942 [9]D. M.Schneider,“Control of processes with time delays ”,IEEE Transactions On Industry Applications,pp.186- 191,1988 [10]B.Tashtoush ,M.Molhim and M.Al-Rousan,“Dynamic model of an HVAC system for control analysis”,Energy,Vol.3 0,pp.1729-1745,2005 [11]J.C.Doyle ,G.Stein,“Multivariable feedback design: Concepts for a classical/modern synthesis”,IEEE Transactions on automatic control,VOL.26(1),pp.4- 16,1981 [12]L.Wang and W.R.Cluett,“Tuning PID controllers for integrating process”,IEEE Control theory and applic ations,Vol.144(5) ,pp.385-392,1997 [13]I.Kaya,N.Tan and D.P.Atherton,“A simple procedure for improveing performance of PID controller”,IEEE proc.of Conf.on Contr.Appl.,pp.882-885,2003 [14]W.K.Ho,K.W.Lim,C.C.Hang,L.Y.Ni,“Getting more phase margin and performance out of PID controllers” , Automatica,Vol.35(9),pp.1579-1585,1999 [15]Z.J.Palmor, D.V.Powers, ,“Improved dead-time compens ator con troller” ,AICHE J.,Vol.31(2),pp.215-221,1 985 [16]W.D.Zhang,Y.X.Sun,“Modified smith predictor for controlling integrator/time delay processes”,Ind. Eng.Chem.Res.,Vol.35,pp.2769-2772,1993 [17]K.J.Astrom,C.C.Hang and B.C.Lim,“A new Smith predic tor for controlling a process with an integrator and long dead-time ” ,IEEE,Trans. On Auto. Cont.,Vol.39 (2),pp.343-344,1993 [18]M.R.Matausek,A.D.Micic,“A modified Smith predictor for controlling a prcess with an integrator and long dead-time”,IEEE Trans.on Auto.Cont.Vol.41 (8),pp. 1603-1606,1999 [19]N. S.Nise,“Control System Engineering ”,Third Edition,ISBN 0-471-36601-3,Wiley. [20]W.K.Ho,C.C.Hang and J.H.Zhou,“Performance and gain phase margins of well-known pi tuning gormulas”, IEEE,Tran.On Auto.Cont.,Vol.3(2),pp.245-248,1995 [21]孔德華;長時延程序雙自由度Smith預測器之設計.國立台灣 大學化學工程研究所,碩士論文,2001
摘要: 
摘 要

空調箱(Air Handling Unit)系統在推導動態方程式中,常因許多假設條件簡化實際物理系統,無法很精準的建構數學模型,且實際的系統存在時間延遲問題,本文中主要目的為探討AHU系統,存在不確定參數及時間延遲控制問題,利用PID控制器時,對含有時間延遲的受控系統,會造成過衝量過大,且反應時間長,且在含有不確定參數時則無法穩定的控制系統,此時若能將模式誤差及時間延遲項所造成的問題,有效的解決,那問題就變得簡單了,本文中利用幅量相位的規範調諧IMC-Simth控制器,能有效解決AHU系統,在系統存在不確定參數時,也能有不錯反應時間且兼具強健性,且本文中所使用的參數調諧方法,理論及計算簡單,易於應用。

Abstract

The AHU (Air Handling Unit)can't be established accurately mathematical model when executing dynamic program because many assumptions simplify real physical system and there are time delay problem existing. The exact mathematical dynamic model of the air handling unit in a air conditioning system can not be established because of many parameters are involved. The purpose of this reserch is to discuss the uncertain parameters and time delay controlled problems in the air AHU. When using PID with time delay controlled system, the overshoot is huge and response time is long. If there are uncertain parameters, the system is unstable. Alfernatively, we use amplitude-phase standard IMC-Smith controller to solve the above problems encurentered AHU system. It is found that even there exist some uncertain parameters in the system, the response time is fast and result is reliscle.
URI: http://hdl.handle.net/11455/1725
其他識別: U0005-2706200612595200
Appears in Collections:機械工程學系所

Show full item record
 

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.