Design and Experimental Analysis of Cooling Structure of an Outside Metallic Box Used for High Capacity Tele-communication System
作者: 王世全
Wang, Shih-Chuan
關鍵字: Outside Metallic Box;屋外機箱;Tele-communication System;電信系統
出版社: 機械工程學系所
引用: 【1】”CPU十年總回顧” 電腦與資訊雜誌p93-p103,93年3月 【2】蔡國清,多孔性散熱結構之設計與實驗分析(Design and Experimental analysis of porouscoolingstructure)國立中興大學機械工程研究所碩士論文,2003 【3】趙隆山等三人,電子元件之三維散熱分析,力學系列B第十五卷第二期,P81- P93中華民國八十八年十二月 【4】陳文亮”電腦散熱扇葉片外型對性能及噪音的影響”中華民國振動與噪音工程學會論文集(2004/06)P150-157 【5】王宏加,鰭管式熱交換器最佳外形之探討(The Study of Optimal Fin Shape for a Finned Tube Heat Exchanger),逢甲大學機械工程研究所碩士論文,93年6月 【6】ADSL網路架構,中華電信股份有限公司教育訓練講義 【7】李霖鴻與宋逸群,新一代屋外型基座式機箱,台灣明尼蘇達礦業製造股份有限公司,3M Taiwan LTD) 【8】盧昭輝副教授,高等熱傳學”High Level of Heat Transfer”上課講義,國立中興大學機械研究所 【9】黃溪泉副教授,流體力學”A Brief Introduction to Fluid Mechanics”上課講義,國立中興大學機械研究所 【10】Kirk D. Hagen “Heat Transfer with Applications” International Edition Charter11 【11】杜鳳棋 譯,流體力學-精華本(A BRIEF INTRODUCTION TO FLIUD MECHANICS)(原著YOUNG MUNSON OKIISHI) 【12】陳信利,矩形鰭片鰭管式熱交換器之熱液動性能研究,成功大學機械研究所,91年,指導教授:張錦裕教授 【13】J.P.Holman”Heat Transfer”Eighth Edition McGraw-Hill Companies p47-p53 【14】張仲卿等四人 譯,熱傳遞(原著Incropera De Witt”Foundamentals of Heat and Mass Transfer) ,4th ed Charter 3 p67-p119
摘要: 
本實驗的主體,為中華電信股份有限公司為了擴大網路的服務範圍,在馬路邊裝設的高容量屋外型電信機箱,分為內外兩層,內層是封閉空間,安裝網路設備,為主要的熱源,外層安裝線路設備與散熱裝置。
本實驗探討高容量屋外型電信機箱的有效散熱設計機構,以空氣為冷卻流體進行散熱實驗,並分析高容量屋外機箱之熱傳效益。內裝350W、600W、850W三種定量熱源,交互搭配使用一到三種散熱機構,即:
(1)側邊的熱交換器
(2)頂端的八個排熱風扇
(3)在內機箱上的強制氣冷(熱沉與風扇的組合)

實驗的結果發現(1)平衡溫度會隨環境溫度而改變(2)強制氣冷可提升散熱效率約6.5%~ 20%(3)可以降低機箱內的平衡溫度,以減少電路板的故障率,同時也可以提升服務品質。

The main object of experiment is built for expanding service area in Chunghwa Telecom Company , LTD. It is a metallic box that is on the side of the road used for High Capacity Tele-communication System. It consists of two layers. Inside layer is installed with internet equipment that is the main heat source. Outside layer is installed with subscriber line and cooling equipment.

The experiment is researched for cooling structure of an outside metallic box used for High Capacity Tele-communication System. The process of experiment is used with air for cooling fluid. Then analyses the effect of heat transfer that cooling structure of an outside metallic box used for High Capacity Tele-communication System Inside layer has three fixed heat source that are 350W,600W and 850W. There are 1 ~ 3 cooling structures that are consist of
(1)heat exchanger on the side of the box
(2)eight cooling fans on the top of the box
(3)forced cooling structure( assemble with heat sinks and fans)

The result of experiment find (1)Balance temperature changes and follows the background temperature. (2)It can create 6.5%~20% effect of heat transfer with forced cooling structure (3)it could reduce the balance temperature and fault rate of circuit board. At the same time , it can advance the service quality.